It is very important to maintain the full efficiency of Cooling Tower across several industries. One of the major and important components in the operation of Cooling Tower is Rotating Part equipment which have the function to cool down and maintain the stability in the system. If someone still in doubt about the component in cooling tower please refer the article that we ever post before about component of cooling tower including Rotating Part and Static Part.
In this article we will mainly focus on the Rotating Part of Cooling tower about each part function, how to maintain it, and the method to inspect it correctly to ensure that your cooling tower is operating at the full efficiency all the time. One of the important equipment in Rotating part that plays an important role in the operation of cooling tower is Gear Box, which we will explain in detail in this article.
Gear Box or Gear Reducer
Gear Box or Gear Reducer play a role to reduce the speed of motor in order to drive the fan in the system. Normally cooling tower used 4-pole motor* to drive the fan blade, which a standard speed of the 4 poles motor at approximately 1,500 rpm. We cannot drive the fan blade straight away because this will cause the tip speed of the Blade (Tip Speed) to be too high. According to the standard of Tip Speed it must not exceed 61 meters per second, in case the Tip Speed higher than this figure, there is a high chance of vibration occur which will cause damage later.
* Poles is the number of magnetic poles that create a magnetic field inside the motor. The more poles there are, the rotational speed of the motor will be lower.
In order to calculate the tip speed of the propeller, the equation will be used as below :
For example, to calculate the propeller tip speed : If the propeller has a diameter of 7.32 meters and rotates with a speed of 150 RPM
Tip Speed = 73.2 * 3.14159 * 150
60
Tip speed = 57.49 m/s
If the calculation of Tip Speed is found out to be more than 61 m/s as specified by the standard, there are 2 options to adjust :
Method 1: Use Gear Box or Gear Reducer to reduce the speed.
There are 3 main types of Gear Reducer :
1. Helical Gear Drive
Picture 1 : Helical Gear Drive
2. Belt Drive
Picture 2 : Belt Drive
3.Right Angle Gear Design
Picture 3 : Right Angle Gear Reducer
Method 2 : Changing the number of Pole Motors
The speed of each pole motor using are as below :
The speed of the motor can be calculated from the below equation
If you want the speed of the motor to be increased or decreased, you can choose the number of motors. We can used various type of poles according to the usage and design of the system that needs to be used and can accurately calculate the motor speed from the above equation. Therefore, this way will help you to select the motor appropriate to the operation.
Therefore, most of the time, Cooling Towers must have Gear Reducer to reduce the motor speed appropriately. It is very important to choose the right motor and gear box together with maintaining it efficiently to ensure the safety of cooling tower system.
How to repair and maintenance a GearBox or Gear Reducer
It is very essential for repairing and maintenance a Gearbox or Gear Reducer need to use the well experienced expertise. The operation consists of the following important steps
The problem in Overhaul Gearbox which we always found is that selection an inexperienced Mechanic who have not enough skill up to the standard will lead to :
Article about a case study of overhaul gearbox >>> Is it true that it won't matter much who fixes the gearbox?
The decision to choosing the Mechanic with inexperience or choosing just because of the price factor will lead to saving money in short term in most cases. It looks like maintenance of the car in the Garage is not up to the standard instead of being taken into the Certified Service Center which have an expert technician to maintain the car.
It is definitely worthwhile in the long run if we invest to choose the technicians who have experience and knowledge for overhaul and maintenance because it helps to ensure that the various components in cooling tower get proper care to reduce the risk of damage or shorter lifetime than it is supposed to be.
Additionally, after Overhaul Gear is completed, it is essential to choose the Service Center that has a Running Test Gear Machine to ensure that the system of sound, temperature and vibration does work well and up to the standard before being brought back to the actual installation and use it. This will help to detect the potential problem in advance, reducing losses, time and expenses from subsequent unnecessary repairs.
Ultimately, choosing the Service Center that has thoroughly tested your device is the best way to prevent it from the problem that may occur and reduce the risk along with the inessential cost for long run.
Last but not least, we do hope that this article will be useful to readers. If you have any questions or query about cooling towers, or have any idea for our next article please contact us or make suggestions through our email coolingexpert@innovek.co.th We are ready to give advice and answer your questions for free from our experienced and well-trained expertise.
If you like our articles and want to follow the next article to ensure you do not miss it, follow us at
Facebook: Innovek Asia
ID Line: @innove
you can click Follow and receive news at the bottom left corner of our website.